First, 500X relief valve structure and use of features:
500X pressure relief / pressure holding valve consists of a main valve, pressure relief / pressure pilot valve needle, ball valve, microfilter and pressure gauge to form a hydraulic control takeover system. The use of hydraulic automatic operation, that can be used for pressure relief valve and pressure valve can be used. For pressure relief valve used to maintain the water supply pressure below the set safety value; do hold pressure valve to maintain the water pressure upstream of the main valve above the set value to maintain water pressure upstream of the main valve.
500X pressure relief valve using hydraulic self-control, do not need other devices and energy, easy maintenance, a valve and more. This series of valve products are widely used in high-rise buildings, living areas and other water supply pipe network systems and urban water supply projects.
Second, 500X pressure relief valve works:
1, as a pressure relief valve: When the pressure relief / pressure relief pilot valve is adjusted state, water needle valve, the main valve control chamber, valve A, relief / holding pressure pilot valve, ball B toward the outlet, at this time Main valve is open. When the inlet pressure exceeds the safety value set by the pressure relief / pressure holding pilot valve, the pressure relief pilot valve will open automatically and release part of the water through the valve C to relieve the pressure in the pipeline. The pressure relief valve closes automatically when the pressure returns to its safe value. For pressure relief valve, the ball valve normally open.
2, as holding pressure valve: When the pressure relief valve / pilot pressure regulator to adjust the state, as long as the main valve inlet pressure below the pilot valve set, pilot valve is closed. The main control room pressure, the main valve is closed. When the main valve supply pressure upstream of the pilot valve exceeds a set pressure, holding pressure to open the pilot valve, the control chamber outlet to discharge water through the ball valve, the control chamber buck main valve, water supply starts, i.e., the upstream pressure maintained. For holding pressure valve, ball valve C is normally closed or replaced with silk plug.
Third, 500X pressure relief valve main technical parameters:
Nominal pressure (Mpa) | Shell test pressure (MPa) | Seal test pressure (MPa) | Suitable media | Medium temperature (℃) |
1.0 | 1.5 | 1.1 | water | 0-80 |
1.6 | 2.4 | 1.76 | ||
2.5 | 3.75 | 2.75 |
Fourth, 500X pressure relief valve main parts and materials:
Part Name | Parts and materials |
Body valve cover | WCB |
Valve seat disc | Copper alloy |
O-ring seals | Nitrile rubber |
Valve stem | 2Cr13 |
spring | 50CrVA |
Needle valve | Copper alloy |
Ball valve | Copper alloy |
Pressure relief / holding pressure pilot valve | Copper alloy |
Micro filter | stainless steel |
Fifth, 500X relief valve installation dimensions:
Fifth, 500X pressure relief valve connection size (PN 1.0-2.5MPa):
Nominal diameter DN | L | H | H1 | A | B |
50 | 250 | 335 | 90 | 170 | 170 |
65 | 280 | 345 | 98 | 180 | 180 |
80 | 310 | 355 | 110 | 190 | 190 |
100 | 350 | 365 | 120 | 200 | 200 |
125 | 400 | 445 | 145 | 215 | 215 |
150 | 450 | 460 | 155 | 230 | 230 |
200 | 550 | 505 | 190 | 255 | 255 |
250 | 650 | 550 | 250 | 295 | 295 |
300 | 800 | 710 | 290 | 325 | 325 |
350 | 900 | 725 | 330 | 380 | 380 |
400 | 1000 | 760 | 360 | 415 | 415 |
450 | 1000 | 810 | 445 | 435 | 435 |
500 | 1100 | 865 | 495 | 460 | 460 |
600 | 1100 | 935 | 550 | 520 | 520 |
700 | 1450 | 1000 | 605 | 570 | 570 |
800 | 1560 | 1100 | 730 | 620 | 620 |
900 | 1800 | 1205 | 800 | 670 | 670 |
1000 | 2000 | 1330 | 910 | 830 | 830 |